Voltage Drop Calculator
Every wire resists current a little, and that resistance steals voltage along the run. On a long circuit the voltage that reaches the load can be several volts below the voltage at the panel — enough to make motors run hot, lights dim and electronics misbehave. This voltage drop calculator works out exactly how much voltage you lose, using the NEC Chapter 9, Table 8 resistance values at 75 °C.
Enter the source voltage, phase, load current, one-way length, wire size and conductor material. The calculator gives you the voltage drop in volts and percent, the voltage at the load, a pass/fail verdict against the NEC 3% branch-circuit guide, and the power lost as heat.

Enter the one-way distance from the source to the load — the factor 2 (single-phase) already counts the return conductor, so entering the round trip doubles the answer.
Aluminum starts at 12 AWG — if 14 AWG is selected, the calculator switches to 12 AWG aluminum.
Conductor resistance: 1.240 Ω/1000 ft
Voltage drop: 4.96 V
Percent drop: 2.07%
Voltage at load: 235.04 V
Verdict (3% branch-circuit guide): PASS
Power lost as heat: 99.2 W
Formula
Single-phase VD = 2 × R × I × L ÷ 1000; three-phase VD = 1.732 × R × I × L ÷ 1000
- R is the conductor DC resistance in ohms per 1,000 ft at 75 °C from NEC Chapter 9, Table 8 (e.g. 10 AWG copper = 1.24 Ω/1000 ft). I is the load current in amps, L is the one-way length in feet.
- The factor 2 counts the out-and-back path on a single-phase circuit; 1.732 (√3) is the three-phase factor. Enter the one-way length, not the round trip — feeding in the loop length doubles the answer.
- % drop = VD ÷ source voltage × 100. Voltage at load = source voltage − VD.
- The NEC recommends no more than 3% drop on a branch circuit and 5% combined feeder + branch — these are Informational Notes, not hard rules, but they are the pass/fail line this tool uses.
- This method uses DC resistance (unity power factor). For large conductors (250 kcmil and up) or poor power factor, NEC Chapter 9, Table 9 AC impedance is more accurate.
Worked Example
Take a 240 V single-phase circuit feeding a 20 A load through 100 ft of 10 AWG copper (R = 1.24 Ω/1000 ft).
- Voltage drop: VD = 2 × 1.24 × 20 × 100 ÷ 1000 = 4.96 V.
- Percent drop: 4.96 ÷ 240 × 100 = 2.07% — under 3%, so it passes.
- Voltage at load: 240 − 4.96 = 235.04 V.
- Power lost as heat: 4.96 × 20 = 99.2 W.
Answer: 4.96 V dropped (2.07%) — 235.04 V reaches the load, PASS vs the 3% guide.
The same load on a 120 V circuit is a different story: 120 V single-phase, 20 A, 100 ft, 12 AWG copper gives VD = 2 × 1.98 × 20 × 100 ÷ 1000 = 7.92 V (6.60%), so only 112.08 V reaches the load — FAIL — and 158.4 W is lost as heat. Lower voltage means the same watts need more current, and the drop is a bigger share of a smaller supply.
Voltage Drop by Wire Size
The same run — 240 V, single-phase, 20 A, 100 ft, copper — on different wire sizes. Dropping one size can be the difference between pass and fail.
| Wire size | R (Ω/1000 ft) | Voltage drop | % drop | Verdict |
|---|---|---|---|---|
| 14 AWG | 3.14 | 12.56 V | 5.23% | FAIL |
| 12 AWG | 1.98 | 7.92 V | 3.30% | FAIL |
| 10 AWG | 1.24 | 4.96 V | 2.07% | PASS |
| 8 AWG | 0.778 | 3.11 V | 1.30% | PASS |
| 6 AWG | 0.491 | 1.96 V | 0.82% | PASS |
Same case in 12 AWG aluminum (R = 3.25): 13.00 V drop, 5.42% — FAIL. Aluminum drops about 64% more than the same copper size.
FAQs
Single-phase: VD = 2 × R × I × L ÷ 1000; three-phase: VD = 1.732 × R × I × L ÷ 1000, where R is the NEC Chapter 9, Table 8 resistance in ohms per 1,000 ft at 75 °C, I is the load current in amps and L is the one-way length in feet. Divide by the source voltage and multiply by 100 for the percentage.
The NEC recommends no more than 3% on a branch circuit and 5% total for feeder plus branch circuit. These are Informational Notes, not enforceable rules — but motors run hot, lights dim and electronics misbehave above them, and most inspectors treat them as the limit.
One-way only — the distance from the source to the load. The factor 2 (single-phase) already accounts for the return conductor, so entering the there-and-back length doubles the answer.
Aluminum resists current more: 12 AWG aluminum is 3.25 Ω/1000 ft against 1.98 for copper, so the same run drops about 64% more volts. You typically need aluminum one to two sizes larger than copper for the same drop.
More Calculators
- Feet and Inches Calculator
- Concrete Calculator
- Board Foot Calculator
- Roofing Calculator
- Deck Calculator
- Paint Calculator
- Tile Calculator
- Flooring Calculator
- Insulation Calculator
- Siding Calculator
- AC Size Calculator
- Stair Calculator
- Fence Calculator
- Drywall Calculator
- Brick Calculator
- Solar Panel Calculator
- Retaining Wall Calculator
- Wallpaper Calculator
- Paver Calculator
Latest Videos
Watch this walkthrough of voltage drop calculations to see both methods — the resistance formula and the NEC tables — worked through on real circuits.