Voltage Drop Calculator

Every wire resists current a little, and that resistance steals voltage along the run. On a long circuit the voltage that reaches the load can be several volts below the voltage at the panel — enough to make motors run hot, lights dim and electronics misbehave. This voltage drop calculator works out exactly how much voltage you lose, using the NEC Chapter 9, Table 8 resistance values at 75 °C.

Enter the source voltage, phase, load current, one-way length, wire size and conductor material. The calculator gives you the voltage drop in volts and percent, the voltage at the load, a pass/fail verdict against the NEC 3% branch-circuit guide, and the power lost as heat.

Voltage Drop Calculator





Enter the one-way distance from the source to the load — the factor 2 (single-phase) already counts the return conductor, so entering the round trip doubles the answer.



Aluminum starts at 12 AWG — if 14 AWG is selected, the calculator switches to 12 AWG aluminum.

Conductor resistance: 1.240 Ω/1000 ft

Voltage drop: 4.96 V

Percent drop: 2.07%

Voltage at load: 235.04 V

Verdict (3% branch-circuit guide): PASS

Power lost as heat: 99.2 W

Formula

Single-phase VD = 2 × R × I × L ÷ 1000; three-phase VD = 1.732 × R × I × L ÷ 1000

  • R is the conductor DC resistance in ohms per 1,000 ft at 75 °C from NEC Chapter 9, Table 8 (e.g. 10 AWG copper = 1.24 Ω/1000 ft). I is the load current in amps, L is the one-way length in feet.
  • The factor 2 counts the out-and-back path on a single-phase circuit; 1.732 (√3) is the three-phase factor. Enter the one-way length, not the round trip — feeding in the loop length doubles the answer.
  • % drop = VD ÷ source voltage × 100. Voltage at load = source voltage − VD.
  • The NEC recommends no more than 3% drop on a branch circuit and 5% combined feeder + branch — these are Informational Notes, not hard rules, but they are the pass/fail line this tool uses.
  • This method uses DC resistance (unity power factor). For large conductors (250 kcmil and up) or poor power factor, NEC Chapter 9, Table 9 AC impedance is more accurate.

Worked Example

Take a 240 V single-phase circuit feeding a 20 A load through 100 ft of 10 AWG copper (R = 1.24 Ω/1000 ft).

  1. Voltage drop: VD = 2 × 1.24 × 20 × 100 ÷ 1000 = 4.96 V.
  2. Percent drop: 4.96 ÷ 240 × 100 = 2.07% — under 3%, so it passes.
  3. Voltage at load: 240 − 4.96 = 235.04 V.
  4. Power lost as heat: 4.96 × 20 = 99.2 W.

Answer: 4.96 V dropped (2.07%) — 235.04 V reaches the load, PASS vs the 3% guide.

The same load on a 120 V circuit is a different story: 120 V single-phase, 20 A, 100 ft, 12 AWG copper gives VD = 2 × 1.98 × 20 × 100 ÷ 1000 = 7.92 V (6.60%), so only 112.08 V reaches the load — FAIL — and 158.4 W is lost as heat. Lower voltage means the same watts need more current, and the drop is a bigger share of a smaller supply.

Voltage Drop by Wire Size

The same run — 240 V, single-phase, 20 A, 100 ft, copper — on different wire sizes. Dropping one size can be the difference between pass and fail.

Wire sizeR (Ω/1000 ft)Voltage drop% dropVerdict
14 AWG3.1412.56 V5.23%FAIL
12 AWG1.987.92 V3.30%FAIL
10 AWG1.244.96 V2.07%PASS
8 AWG0.7783.11 V1.30%PASS
6 AWG0.4911.96 V0.82%PASS

Same case in 12 AWG aluminum (R = 3.25): 13.00 V drop, 5.42% — FAIL. Aluminum drops about 64% more than the same copper size.

FAQs

How do you calculate voltage drop?

Single-phase: VD = 2 × R × I × L ÷ 1000; three-phase: VD = 1.732 × R × I × L ÷ 1000, where R is the NEC Chapter 9, Table 8 resistance in ohms per 1,000 ft at 75 °C, I is the load current in amps and L is the one-way length in feet. Divide by the source voltage and multiply by 100 for the percentage.

What is an acceptable voltage drop?

The NEC recommends no more than 3% on a branch circuit and 5% total for feeder plus branch circuit. These are Informational Notes, not enforceable rules — but motors run hot, lights dim and electronics misbehave above them, and most inspectors treat them as the limit.

Do I enter the one-way length or the round trip?

One-way only — the distance from the source to the load. The factor 2 (single-phase) already accounts for the return conductor, so entering the there-and-back length doubles the answer.

Why does aluminum drop more voltage than copper?

Aluminum resists current more: 12 AWG aluminum is 3.25 Ω/1000 ft against 1.98 for copper, so the same run drops about 64% more volts. You typically need aluminum one to two sizes larger than copper for the same drop.