Wire Ampacity Calculator

Use this Wire Ampacity Calculator to find the maximum current a wire can safely carry — its ampacity — from NEC Table 310.16, and to find the smallest conductor that carries a given load. It applies the 125% continuous-load rule, ambient-temperature correction, bundling adjustment, the termination-temperature limit and the small-conductor breaker caps, for copper and aluminum.

It completes the trio with the Wire Size Calculator and the Voltage Drop Calculator — the same tables, the same rules. A size that passes the ampacity check can still fail on voltage drop over a long run, so check both. All values are NEC 2023, Table 310.16 (75 °C column). Local amendments and the authority having jurisdiction (AHJ) govern — this is a planning tool, not a substitute for a licensed electrician.

Wire Ampacity Calculator

Result: Smallest conductor: 8 AWG copper

Design current: 50.0 A

Base ampacity (Table 310.16, 75 °C): 50 A

Ambient factor: ×1.00

Bundling factor: ×1.00

Termination cap: 50 A (75 °C column)

Usable ampacity: 50.00 A

Headroom: 0.0 A

Max breaker (NEC 240.4(D)): —

Verdict: Fits — usable ampacity covers the design current.

Formula

Required ampacity ≥ 125% × continuous load + 100% × noncontinuous load; usable ampacity = Table 310.16 value × ambient factor × bundling factor

  • Base ampacity comes from NEC Table 310.16, 75 °C column (≤ 3 conductors, 30 °C ambient).
  • Ambient correction, Table 310.15(B)(1), 75 °C column: 21–25 °C ×1.05, 26–30 °C ×1.00, 31–35 °C ×0.94, 36–40 °C ×0.88, 41–45 °C ×0.82, 46–50 °C ×0.75.
  • Bundling adjustment, Table 310.15(C)(1): 4–6 conductors ×0.80, 7–9 ×0.70, 10–20 ×0.50, 21–30 ×0.45.
  • Termination limit, NEC 110.14(C): the usable ampacity is the lower of the corrected value and the column matching the equipment's terminal rating (60 °C, 75 °C or 90 °C).
  • Small-conductor breaker caps, NEC 240.4(D): copper 14 AWG max 15 A, 12 AWG 20 A, 10 AWG 30 A; aluminum 12 AWG 15 A, 10 AWG 25 A.
  • Rooftop-conduit +33 °C adder (NEC 310.15(B)(2)) is out of scope for v1.
  • All values are NEC 2023. Local amendments and the AHJ govern.

Worked Example

A 40 A continuous load on a copper circuit with 75 °C terminations, 30 °C ambient and 3 or fewer conductors in the raceway. What is the smallest conductor?

  1. Design current: a continuous load is sized at 125% — 40 × 1.25 = 50.0 A.
  2. Smallest copper at 75 °C with a table ampacity of at least 50 A: 8 AWG (50 A).
  3. Derating: 30 °C ambient ×1.00 and 3 or fewer conductors ×1.00 — usable ampacity 50 × 1.00 × 1.00 = 50.00 A.
  4. Termination: 75 °C terminals cap the usable ampacity at the 75 °C column value, 50 A — no reduction.
  5. Headroom: 50.00 − 50.0 = 0.0 A.

Answer: 8 AWG copper — usable ampacity 50.00 A, headroom 0.0 A. It exactly carries the load.

Non-continuous case: a 30 A load that is not continuous needs no 125% factor — design current 30 A — so the smallest copper is 10 AWG (35 A table), headroom 5 A. The breaker on 10 AWG is still capped at 30 A by NEC 240.4(D).

Derating case: the same 8 AWG copper at 40 °C ambient with 4–6 conductors bundled gives 50 × 0.88 × 0.80 = 35.20 A usable — a 40 A continuous load (50 A design) does not fit it, and the widget sizes up to 4 AWG copper.

Aluminum case: a 40 A continuous load on aluminum needs a 50 A design current — the smallest aluminum at 75 °C is 6 AWG (50 A).

NEC Table 310.16 Ampacity (75 °C Column)

Base ampacity in amperes from NEC Table 310.16, 75 °C column, for copper and aluminum conductors (not more than three current-carrying conductors in a raceway, 30 °C ambient). The last column is the NEC 240.4(D) maximum overcurrent protection for small conductors.

Gauge (AWG)Copper (A)Aluminum (A)Max breaker, 240.4(D) (A)
1420—15 (Cu)
12252020 (Cu) / 15 (Al)
10352530 (Cu) / 25 (Al)
85040—
66550—
48565—
3100——
211590—
1130——
1/0150120—
2/0175——
3/0200——
4/0230180—

Aluminum has no 14 AWG row, and no 3, 1, 2/0 or 3/0 AWG rows in this table — the same gap the Wire Size Calculator works around. The 75 °C column is the one to use unless the equipment terminals are rated otherwise (see the termination limit above).

Latest Videos

Watch this walkthrough of NEC Table 310.16 and conductor protection (NEC 240.4) — how to read the ampacity table and why the small-conductor caps matter:

FAQs

What is ampacity?

The most current a wire can carry continuously without its insulation overheating: 8 AWG copper is rated 50 A at 75 °C — push past it and the insulation degrades.

Why size a 40 A load at 50 A?

Continuous loads (3+ hours) must be sized at 125% under NEC 210.19(A)(1) — the wire runs hot for hours, so it needs the headroom.

Why does hot weather or bundling lower the rating?

Heat can't escape: 40 °C ambient drops 8 AWG from 50 A to 44 A, and 4–6 bundled conductors drop it to 35.20 A.

Can I use the 90 °C column?

Only if the equipment terminals are rated 90 °C — most are 75 °C or 60 °C, and NEC 110.14(C) says the terminal rating caps the column you may use.