Wire Size Calculator
Picking a wire size is two checks, not one. The wire has to carry the current without overheating — that is ampacity — and it has to keep the voltage drop under the limit on a long run. A size that passes one check can easily fail the other, so this wire size calculator runs both NEC checks and recommends the larger of the two minimums.
Enter the load current, whether it is continuous, the voltage, phase, one-way length, conductor material and the maximum voltage drop you will accept. The calculator sizes the wire by Table 310.16 ampacity (75 °C column, with the NEC 240.4(D) caps) and by Chapter 9, Table 8 voltage drop, then recommends the thicker of the two.

A continuous load is sized at 125% of the load current (NEC 210.19(A)(1)).
Aluminum starts at 12 AWG.
Design current: 50 A
Minimum AWG by ampacity: 8 AWG
Minimum AWG by voltage drop: 6 AWG
Recommended AWG: 6 AWG copper
Ampacity of recommended size: 65 A
Resulting voltage drop: 2.46% (5.89 V)
Formula
Recommended AWG = the larger of (smallest size meeting ampacity) and (smallest size keeping voltage drop ≤ 3%)
- Ampacity step: design current = 1.25 × load current for a continuous load (NEC 210.19(A)(1); continuous = 3 hours or more), otherwise the load current. Pick the smallest AWG whose Table 310.16 75 °C ampacity meets it — after the NEC 240.4(D) caps (copper 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A; aluminum 12 AWG 15 A, 10 AWG 25 A).
- Voltage-drop step: using the ACTUAL load current (not the 125% design current) and the NEC Chapter 9, Table 8 resistances, pick the smallest AWG with VD ≤ the max % (default 3%): single-phase VD = 2 × R × I × L ÷ 1000, three-phase VD = 1.732 × R × I × L ÷ 1000.
- The recommended size is the larger (thicker) of the two — a wire that is big enough for the current can still fail on a long run, and vice versa.
- Table values assume ≤ 3 current-carrying conductors at 30 °C ambient. This tool does not derate for bundling, hot attics or 60 °C terminations — those need the full NEC tables and, for real work, a licensed electrician.
Worked Example
Take a 40 A continuous load on a 240 V single-phase circuit, 150 ft one-way, copper, with a 3% maximum drop.
- Design current: 40 × 1.25 = 50 A. Smallest copper size with 75 °C ampacity ≥ 50 A is 8 AWG (50 A) — exactly enough.
- Voltage drop at 8 AWG (actual 40 A): VD = 2 × 0.778 × 40 × 150 ÷ 1000 = 9.34 V = 3.89% — over 3%, so 8 AWG fails on drop.
- Next size up, 6 AWG: VD = 2 × 0.491 × 40 × 150 ÷ 1000 = 5.89 V = 2.46% — passes. Minimum by voltage drop is 6 AWG.
- Recommended = larger of 8 AWG (ampacity) and 6 AWG (drop) = 6 AWG, ampacity 65 A, resulting drop 2.46%.
Answer: use 6 AWG copper — 8 AWG carries the current but drops 3.89%, over the 3% limit.
A shorter, lighter case shows the other side: a 20 A non-continuous load on 120 V, 100 ft, copper, 3% max. The design current is 20 A (no 125% factor), so the ampacity minimum is 12 AWG (25 A table, 20 A cap — exactly enough). But on voltage drop, 12 AWG gives 7.92 V (6.60%) and 10 AWG gives 4.96 V (4.13%) — both fail — so the minimum by drop is 8 AWG at 3.11 V (2.59%). Recommended: 8 AWG copper (50 A), 2.59% drop. (Some sites recommend 10 AWG for this case quoting a 3.9 V / 3.3% drop — but 3.3% is over the 3% limit. 8 AWG is the correct minimum.)
Recommended AWG by Load and Length
Copper, 240 V single-phase, continuous load, 3% maximum drop. The design current is the load × 1.25.
| Load | One-way length | Design current (×1.25) | Min by ampacity | Min by voltage drop | Recommended | Ampacity | Resulting % drop |
|---|---|---|---|---|---|---|---|
| 20 A | 50 ft | 25 A | 10 AWG | 14 AWG | 10 AWG | 30 A | 1.03% |
| 20 A | 150 ft | 25 A | 10 AWG | 8 AWG | 8 AWG | 50 A | 1.95% |
| 30 A | 100 ft | 37.5 A | 8 AWG | 8 AWG | 8 AWG | 50 A | 1.95% |
| 40 A | 150 ft | 50 A | 8 AWG | 6 AWG | 6 AWG | 65 A | 2.46% |
| 50 A | 100 ft | 62.5 A | 6 AWG | 6 AWG | 6 AWG | 65 A | 2.05% |
| 60 A | 200 ft | 75 A | 4 AWG | 3 AWG | 3 AWG | 100 A | 2.45% |
The 20 A rows show the 240.4(D) trap — the design current is 25 A, and 12 AWG copper has a 25 A table ampacity but is capped at 20 A, so the ampacity minimum is 10 AWG, not 12 AWG. Ampacity shown is the usable ampacity after the 240.4(D) cap (10 AWG = 30 A, not its 35 A table value).
Aluminum for the worked example (40 A continuous, 240 V, 150 ft): ampacity min 6 AWG Al (50 A), voltage-drop min 4 AWG Al (6.10 V = 2.54%), recommended 4 AWG aluminum — two sizes up from copper.
FAQs
For a short run, 12 AWG copper (20 A breaker per NEC 240.4(D)). On a long run the answer changes: at 100 ft on 120 V, 12 AWG drops 6.60% and even 10 AWG drops 4.13% — you need 8 AWG to stay under 3%. Ampacity and voltage drop are two separate checks, and the larger wire wins.
NEC 210.19(A)(1): conductors (and breakers) for a load running 3 hours or more must be sized at 125% of that load. A 40 A continuous load needs a conductor rated for at least 50 A — 8 AWG copper, not 10 AWG.
NEC 240.4(D) caps the overcurrent protection for small conductors: 14 AWG to 15 A, 12 AWG to 20 A, 10 AWG to 30 A (copper). The 25 A table value is the conductor’s thermal ampacity; the breaker limit is the binding number on a branch circuit.
Voltage drop uses the ACTUAL load current — the 125% factor is a thermal safety margin for ampacity, not extra current flowing in the wire. Using 125% for the drop check would oversize the wire by a step on long runs.
More Calculators
- Feet and Inches Calculator
- Concrete Calculator
- Board Foot Calculator
- Roofing Calculator
- Deck Calculator
- Paint Calculator
- Tile Calculator
- Flooring Calculator
- Insulation Calculator
- Siding Calculator
- AC Size Calculator
- Stair Calculator
- Fence Calculator
- Drywall Calculator
- Brick Calculator
- Solar Panel Calculator
- Retaining Wall Calculator
- Wallpaper Calculator
- Paver Calculator
- Voltage Drop Calculator
Latest Videos
Watch this tutorial from Encore Wire on how a wire size and voltage drop calculator works — sizing a conductor for both ampacity and voltage drop.